IXOSIL Outdoor Cable Termination (Composite)



Type ESS terminations are available for voltages from 72,5 kV to 300 kV with various creepage distances. A resin-glass fibre tube equipped with silicone sheds gives the ESS termination the highest mechanical strength. The ESS termination can withstand the effects of high forces – in a shortcircuit for example. Insulation within the resin-glass fibre tube is ensured by a filling compound. An easy-to-fit head fitting completes the ESS to provide a maintenance-free system.
IXOSIL Outdoor Cable Termination (Composite)

Max. working voltage Um (kV) 72,5 123 145 170 245 300
Standards       IEC60840
IEC60815
  IEC60840
IEC60815
  IEC60840
IEC60815
IEC60840
IEC60815
  IEC62067
IEC60815
  IEC62067
IEC60815
Rated voltage   U (kV)   60 – 69   110 – 115   132 – 138 150 – 161   220 – 230   275 – 287
Nominal withstand
lightning impulse voltage
  (kV)   325   550   650 750   1050   1050

IXOSIL Outdoor Cable Termination (Porcelain)


The ESP termination can be supplied for voltages from 72,5 kV to 300 kV. The stress cone of the ESP and the ESS termination is identical. Specifications mentioned for ESS are valid as well.
IXOSIL Outdoor Cable Termination (Porcelain)
Max. working voltage Um (kV) 72,5 123 145 170 245 300
Standards       IEC60840
IEC60815
  IEC60840
IEC60815
  IEC60840
IEC60815
IEC60840
IEC60815
  IEC62067
IEC60815
  IEC62067
IEC60815
Rated voltage   U (kV)   60 – 69   110 – 115   132 – 138 150 – 161   220 – 230   275 – 287
Nominal withstand
lightning impulse voltage(BIL)
  (kV)   325   550   650 750   1050   1050

IXOSIL Flexible Outdoor Cable Termination


Type ESF flexible terminations are dry, slip-on terminations for modular assembly. The use of silicone sheds makes them ideally suited for applications in outdoor installations. Type ESF terminations are available for voltages from 52 kV to 145 kV.
IXOSIL Flexible Outdoor Cable
Termination
Max. working voltage Um (kV) 52 72,5 123 145
Standards       IEC60840
IEC60815
  IEC60840
IEC60815
  IEC60840
IEC60815
IEC60815
Rated voltage   U (kV)   45 – 47   60 – 69   110 – 115 132 – 138
Nominal withstand
lightning impulse voltage(BIL)
  (kV)   250   325   550 550

IXOSIL Outdoor Cable Termination (Dry Type)


Type EST is ideally suited for out- and indoor. It is available for voltages from 72,5 kV to 145 kV and consists of one flexible termination of type ESF and with one or three supporting insulators, depending on the operating voltage. It is free from liquid insulating materials, can be installed in each position and is self-supporting. The EST is built up modular which permits a fast and simple installation. There is no need for a special platform for fitting the terminations, just a protection against wind and weather. The baseplate is dedsigned to fit on several existing support structures without any problems.
IXOSIL Outdoor Cable Termination (Dry Type)
Max. working voltage Um (kV) 72,5 123 145
Standards       IEC60815
IEC60840
  IEC60815
IEC60840
IEC60815
Rated voltage   U (kV)   60 – 69   110 – 115 132 – 138
Nominal withstand
lightning impulse voltage(BIL)
  (kV)   325   550 550

IXOSIL Flexible Indoor Cable Termination

Type ESK terminations are dry, slip-on terminations for modular assembly. The use of silicone sheds makes them ideally suited for applications in indoor installations. Type ESK terminations are available for voltages of 52 kV and 72.5 kV.
IXOSIL Flexible Indoor Cable Termination
Max. working voltage Um (kV) 52 72,5
Standards       IEC60815   IEC60815  
Rated voltage   U (kV)   45   60  
Nominal withstand
lightning impulse voltage(BIL)
  (kV)   250   350  
 
CABLE SYSTEMS | COMPONENTS | OVERHEAD LINES | RAILWAY CATENARY SYSTEMS
Sitemap | Legal information | © 2009 PFISTERER Kontaktsysteme GmbH